tray or it may be located outside of the air curtain. If the air
curtain is unheated, or the sensor will be left in the wiring
tray, skip to step E, otherwise continue.
1. Remove the ½” bushing taped to the back of the
wiring tray cover and set aside.
2. Determine mounting location of the temperature
sensor (do not mount at this time).
3. Choose end of the wiring tray that the sensor will exit
the air curtain based on the mounting location from
F. Proceed to Section V - Electrical Connections.
V. ELECTRICAL CONNECTIONS
All electrical wiring and connections MUST be performed by
qualied personnel in accordance with the National Electri-
cal Code ANSI/NFPA No. 70 (latest edition) or, in Canada, the
Canadian Electrical Code, Part 1-C.S.A. Standard C22.1 and local
codes and regulations.
FIGURE 4 - Installing Air Door on Wall Mounting Plate
A. Check the rating nameplate on the top of the air curtain for
supply voltage and current requirements. See Figure 7.
A separate line voltage supply with a suitable branch circuit
protection device should be run directly from the main
electrical panel to the air curtain. A disconnect switch for
each branch circuit is a required part of this installation.
See Tables 2 & 3.
B. All eld wiring must be copper with a minimum insulation
of 60° C within approved conduit. If any of the wire
supplied with the air curtain must be replaced, it must be
replaced with copper wiring with a minimum insulation of
90° C.
C. Remove the wiring tray cover; on air curtains that are
comprised of modules, remove the wiring tray cover that is
located closest to the electrical rating nameplate (if it has
not already been done).
D. Electric, steam and hot water heated air curtains are factory
equipped with a air curtain mounted solid state
temperature sensor cable (for the Intelliswitch thermostat)
located in the wiring tray. Depending where the tempera
ture is to be measured, the sensor may be left in the wiring
FIGURE 5 - Wall Mounting Plate Storage
FIGURE 6 - Suspended Mounting
4
Step 2.
4. Locate the /” hole on the wiring tray next to
the electrical knockout on the side determined in
Step 3.
5. Drill out the /” hole to ½”.
CAUTION: DO NOT DAMAGE EXISTING WIRES IN
THE WIRING TRAY WHEN DRILLING.
6. Maneuver the tip of the temperature sensor from
the inside of the wiring tray out through ½” hole.
7. Thread the tip through ½” bushing from Step 1 and
snap the bushing into the wiring tray.
8. Mount the temperature sensor. Do not put any clamps
on the rubber coated tip.
E. The top of the air curtain has two knockouts on each side
of the air curtain, allowing for a left hand or right hand
power connection. Remove the required knockout if it has
not already been done and connect the power supply to
the air curtain. Connect all supply and control circuit wires
according to the wiring diagram provided.
NOTE: For Electric heated air curtains provided with the
optional remote thermostat, mount and wire the
thermostat according to instructions and wiring
diagram.
F. Master/Slave connection, if two or more units are to be
linked together for master/Slave operation continue, other-
wise skip to step G.
Vedere la pagina 3
1 2 3 4 5 6 7 8 9 ... 19 20

Commenti su questo manuale

Nessun commento

SBS TABOOKTABS105K manuales

Manuales del propietario y guías del usuario para Casos de tabletas SBS TABOOKTABS105K.
Ofrecemos 1 manuales en pdf SBS TABOOKTABS105K para descargar gratis por tipos de documentos: Ficha de datos






Más productos y manuales para Casos de tabletas SBS

Modelos Tipo de documento
TABOOKTABS84K Ficha de datos   SBS BOOK, 2 paginas
TABOOKIPA6K Ficha de datos   SBS BOOK, 2 paginas
TABOOKSTYLEIPA6K Ficha de datos   SBS BOOK, 2 paginas
TABOOKTAB48K Ficha de datos   SBS TABOOKTAB48K, 2 paginas
TABOOKUN9K Ficha de datos   SBS TABOOKUN9K, 2 paginas
TABOOKUN7S Ficha de datos   SBS TABOOKUN7S, 2 paginas
TABOOKUN7B Ficha de datos   SBS TABOOKUN7B, 2 paginas
TABOOKUN8R Ficha de datos   SBS TABOOKUN8R [en] , 2 paginas
TABOOKTAB47K Ficha de datos   SBS TABOOKTAB47K, 2 paginas
TABOOKUN8B Ficha de datos   SBS TABOOKUN8B, 2 paginas
TABOOKUN8K Ficha de datos   SBS TABOOKUN8K, 2 paginas
TABOOKUN7SG Ficha de datos   SBS TABOOKUN7SG, 2 paginas
TABOOKSTYLETAB47W Ficha de datos   SBS TABOOKSTYLETAB47W, 2 paginas
TABOOKU10P Ficha de datos   SBS TABOOKU10P, 2 paginas
TABOOKU10B Ficha de datos   SBS TABOOKU10B, 2 paginas
TABOOKTAB410K Ficha de datos   SBS TABOOKTAB410K, 2 paginas
TABOOKUN7K Ficha de datos   SBS TABOOKUN7K, 2 paginas
EM0TBL10K Ficha de datos   SBS EM0TBL10K, 2 paginas
TABOOKUN7P Ficha de datos   SBS TABOOKUN7P, 2 paginas
EM0TSC84K Ficha de datos   SBS Entry, 2 paginas